Installation
April 2020 4-52 06-237619-001
4-24.1 Pilot Line Test
After installation, check the complete pilot line arrangement for integrity. Perform this check
as follows:
1. Place the control panel in manual mode.
2. Unscrew the discharge hoses from the top of each cylinder valve.
3. Fit anti-recoil cap (P/N 38-400011-001) to each cylinder valve discharge outlet, applying
correct torque.
4. Operate the system manually either by manual electric release at the control panel or by
the manual release on the release unit.
5. Make sure that the pins are now protruding out from the top of the anti-recoil caps on top
of each cylinder valve.
6. Leak test all connections on the pilot line.
7. Reset manual release unit by turning lever to close position, insert pin, and fix new anti-
tamper seal, or rest manual release at control panel.
8. De-pressurise pilot line by removing the Pilot Line Bleed Valve on the last cylinder valve.
9. Make sure the pins have fully retracted on the top of each anti-recoil cap. Once retracted,
install the Pilot Line Bleed Valve. Make sure to push the actuation hose in fully.
10. Remove the anti-recoil caps from the top of each cylinder valve and reconnect the dis-
charge hoses.
11. Place control panel back to automatic mode.