Maintenance
April 2020 6-10 06-237619-001
6-6.8 Inspect Flexible Hoses
In accordance with NFPA 2001, 2015 Edition, all system hoses shall be examined annually
for damage. If the visual examination shows any deficiencies, replace the hose.
6-6.9 Verify Odorizer Assembly
Verify the odorizer assembly as follows:
1. Remove the odorizer assembly.
2. Check to make sure the burst disc is intact.
3. Reattach the odorizer assembly. If the burst disc has ruptured, replace the odorizer.