System Design
06-237619-001 3-13 April 2020
3-9 CYLINDER CONTENT
At a filling pressure of 200/300 bar at ref. temperature 15°C, standard cylinders will allow the
listed quantity of Agent to be released. The listed values exclude the quantity of gas remaining
in the cylinder after valve closed:
Note: Cylinders may have a nominal volume variation of +5-0%. This may result in a variation
in filling weight and/or resulting filling pressure.
Table 3-8. Kidde IGS IG-100
Cylinder Volume
(liters)
Nominal Filling
200 bar
Nominal Filling
300 bar
80 39.33 lb
17.84 kg
54.3 lb
24.63 kg
Table 3-9. Kidde IGS IG-55
Cylinder Volume
(liters)
Nominal Filling
200 bar
Nominal Filling
300 bar
80 50.33 lb
22.83 kg
70.79 lb
32.11 kg