06-237619-001 i April 2020
FOREWORD
This manual is written for those who design, install, operate, or maintain the Kidde Fire Systems Inert Gas
Engineered Fire Suppression System (Kidde
®
IGS) using IG-55 or IG-100 (herein refer to collectively as
the “Agent”) manufactured after June 2018. For Kidde
®
Argonite
®
Engineered Fire Systems manufactured
prior to July 2018, see DIOM P/N: 06-236432-001. For Kidde Nitrogen Engineered Fire Systems
manufactured prior to July 2018, see DIOM P/N: 06-237459-001.
IMPORTANT
Kidde Fire Systems assumes no responsibility for the application of any systems other than those addressed
in this manual. The technical data contained herein is limited strictly for information purposes only.
Kidde Fire Systems believes this data to be accurate, but it is published and presented without any
guarantee or warranty whatsoever. Kidde Fire Systems disclaims any liability for any use that may be made
of the data and information contained herein by any and all other parties.
Kidde IGS is to be designed, installed, inspected, maintained, tested and recharged by authorized, trained
personnel in accordance with the following:
Standard of the National Fire Protection Association No. 2001, Edition 2015 titled Clean Agent Fire
Extinguishing Systems.
ISO 14520, BS EN 15004 and any other applicable national standards
All instructions, limitations, cautions, and warnings, contained in this manual, 06-237619-001.
All information contained on the system container nameplate(s).
Storage, handling, transportation, service, maintenance, recharge, and test of Agent storage containers
shall be performed only by qualified and trained personnel in accordance with the information in this
manual and Compressed Gas Association pamphlets C-1, C-6 and P-1:
C-1, Methods for Hydrostatic Testing of Compressed Gas Cylinders.
C-6, Standards for Visual Inspection of Compressed Gas Cylinders.
P-1, Safe Handling of Compressed Gases In Containers.
CGA pamphlets are published by the Compressed Gas Association: http://www.cganet.com
All personnel should be trained by Kidde Fire Systems and should have attended a Cylinder
Handling/Installation training session provided by Kidde Fire Systems.
For additional reference information refer to:
National Fire Protection Association (USA): www.nfpa.org
Fire Industry Association (UK): www.fia.uk.com
The design concentration for Class A and C fires applies to systems designed to meet and comply with
FM5600, and NFPA 2001, Edition 2015 requirements. As such, our customers are reminded and advised:
In accordance with 4.3.1.2 and 4.3.1.3 of NFPA 2001, Edition 2015, automatic detection and
automatic actuation shall be used. Manual actuation is permitted only if acceptable by the authority
having jurisdiction.
Designers should also take note of 4.3.5.6 in NFPA 2001, Edition 2015 with regard to discharge
delays.
The designer should also review A.5.4.2.4 in NFPA 2001, Edition 2015 and confirm that a protected
Class A hazard does not include any Class B materials (flammable or combustible liquids or gases)
which would classify the protected space as a Class B hazard.
In addition, the designer should refer to section A.5.6 in NFPA 2001, Edition 2015 and confirm that
the protected space does not include electrical equipment that will not be de-energized prior to or at
the time of Agent discharge. Such energized electrical equipment has the potential to act as a
persistent re-ignition source. If electrical equipment cannot be de-energized, the design Agent
concentration shall be at least that required by 5.4.2.5 in NFPA 2001, Edition 2015. In some cases
consideration should be given to the use of extended Agent discharge or higher design Agent
concentration. When exploring these options, keep in mind the possibility of the formation of
combustion and decomposition products. Please contact applications engineering for design guidance
in such instances.