8 Options
31 Text number Encoding see table in chapter 8.5.4.18 Allocation of the Texts to
the Text Numbers
32 State information 1 Encoding see table in chapter 8.5.4.17 State Information
33 State information 2 Encoding see table in chapter 8.5.4.17 State Information
34 State information 3 Encoding see table in chapter 8.5.4.17 State Information
35 Parameter of state information 1 Encoding see table in chapter 8.5.4.17 State Information
36 Parameter of state information 2 Encoding see table in chapter 8.5.4.17 State Information
37 Operating hours in total Hi
38 Operating hours in total Lo
39 Operating hours curve set 1 Hi
40 Operating hours curve set 1 Lo
41 Operating hours curve set 2 Hi
42 Operating hours curve set 2 Lo
43 Actual value channel 1 Range: 0 ... 999 unsigned
44 Actual value channel 2 Range: 0 ... 999 unsigned
45 Actual value channel 3 Range: 0 ... 999 unsigned
46 Actual value channel 4 Range: 0 ... 999 unsigned
47 Additional information on the text numbers
48 Reserved
49 Setpoint value channel 1 Range: 0 ... 999 unsigned
50 Setpoint value channel 2 Range: 0 ... 999 unsigned
51 Setpoint value channel 3 Range: 0 ... 999 unsigned
52 Setpoint value channel 4 Range: 0 ... 999 unsigned
53 Reserved
54 Correction value 2 Value in 0,1 % unsigned, Range: 0 ... 999
55 Reserved
56 CO/O
2
Operating status Encoding see table in chapter 8.5.4.16 Bit Encoding: Operating
Condition CO/O
2
57 Firing rate default Range: 0 ... 999 unsigned
58 Firing rate default Value: always 0 with BT300
59 FMS Fuel 0x80 = Gas; 0x02 = Oil
60 Digital output: Actual value is above the
threshold
Bit 0 = 1: Switch-on point is reached
61 Digital output: Contactor for curve set
changeover
Bit 0 = 1: Contact
62 Threshold burner ON Range: 0 ... 999 unsigned
63 Threshold burner OFF Range: 0 ... 999 unsigned
EBM100 - Status Information
90 ... 999 EBM Status information Encoding see table in chapter 8.5.4.1 Bit Encoding: Status
Operating Hours, Startup
100 Startup counter curve set 1 Hi
101 Startup counter curve set 1 Lo
102 Startup counter curve set 2 Hi
103 Startup counter curve set 2 Lo
104 ... 199 Reserved
LCM - Data