233
8 Options
Tab. 8-10 Life code data
8.5.4.2 Bit Encoding: Operating Mode
Tab. 8-11 Bit pattern operating mode
8.5.4.3 Bit Encoding: Digital Inputs
Tab. 8-12 Bit encoding of the digital inputs BT300/(BC300
Firing rate controller module
(BT300 only)
LCM100 0 ... 3 70
1 Bit 0 ... 5 – Device-ID: This information is of no relevance for the fieldbus application.
Device Type LSB Family Bit 6 ... Bit 7
1
Device Type or Group Byte 2
Operating Mode Bit Pattern
1
Power ON XXXX 0000 0000 0001
Burner OFF XXXX 0000 0000 0010
Burner STANDBY XXXX 0000 0000 0100
Pre-purge XXXX 0000 0000 1000
Running to ignition position XXXX 0000 0001 0000
Ignition process XXXX 0000 0010 0000
Base fire XXXX 0000 0100 0000
Control mode XXXX 0000 1000 0000
Post-purge XXXX 0001 0000 0000
Fault XXXX 0010 0000 0000
O
2
setting 0001 XXXX XXXX XXXX
Parameter setting 0010 XXXX XXXX XXXX
Setting 0100 XXXX XXXX XXXX
Clear memory 1000 XXXX XXXX XXXX
1 In 0xF000 and 0x0FFF only 1 bit may be set.
BT300
Bit Pattern
HEX Code
Curve set selection 1 = curve set 1 XXXX XXXX XXXX XXX1 0x0001
Ignition position acknowledgement XXXX XXXX XXXX XX1X 0x0002
Gas pressure > min. XXXX XXXX XXXX X1XX 0x0004
Air pressure monitor XXXX XXXX XXXX 1XXX 0x0008
External high fire acknowledgement (always 1) XXXX XXXX XXX1 XXXX 0x0010
Firing rate + XXXX XXXX XX1X XXXX 0x0020
Safety interlock chain curve set 1 XXXX XXXX X1XX XXXX 0x0040
Safety interlock chain system XXXX XXXX 1XXX XXXX 0x0080
Main flame XXXX XXX1 XXXX XXXX 0x0100
Oil pressure > min XXXX XX1X XXXX XXXX 0x0200
firing rate - XXXX X1XX XXXX XXXX 0x0400
Safety interlock chain curve set 2 XXXX 1XXX XXXX XXXX 0x0800
Control release (always 1) XXX1 XXXX XXXX XXXX 0x1000
Fault reset XX1X XXXX XXXX XXXX 0x2000
Burner ON X1XX XXXX XXXX XXXX 0x4000
Pre-purge suppression 1XXX XXXX XXXX XXXX 0x8000