231
8 Options
8.5.4 Appendix
8.5.4.1 Bit Encoding: Status
Status
21 Leakage test post-purge 2 gas
22 Leakage test post-purge 1 gas
24 Ignition without pilot burner gas, safety time 2 is running
25 Ignition without pilot burner gas, safety time 2 has expired
27 MAINTENANCE MODE GAS
29 Pre-purge oil
30 Ignition position oil
31 Ignition transformer oil
32 Ignition oil line safety interlock circuit
33 Ignition pilot burner oil
34 Ignition oil safety time 1 has expired
36 Ignition oil safety time 2 is running
37 Controlling base load oil
43 Switching OFF oil valve
44 Oil is switched OFF
49 Ignition without pilot burner, safety time 2 is running
50 Ignition without pilot burner, safety time 2 has expired
52 MAINTENANCE MODE OIL
111 Fault
113 Power ON
114 Cold check
200 Switched OFF, post-purge gas
201 Switched OFF, post-purge oil
Value Description
Module Byte Pos. Description/Configuration
1 154 + 155 BT300software version the first two digits (e.g. 2.2)
1 156 + 157 BT300Status Encoding see table in chapter Status
1 158 + 159 BT300Warning Encoding see table in chapter Warnings
1 160 + 161 BT300Fault Encoding see table in chapter Faults
1 162 + 163 Life code burner control Encoding see table in chapter Life Code Data
1 164 + 165 Life code LT Encoding see table in chapter Life Code Data
1 166 + 167 Life code LCM Encoding see table in chapter Life Code Data
1 168 + 169 Reserved
1 170 + 171 Reserved
1 172 + 173 Reserved
Status Description
0 Fault