IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
5-13
LOC/REM Run Select
If the run reference/speed reference are switched between serial mode and drive terminal mode,
B03.07 determines action after the switch.
Parameter
Code Name Function Range
Initial
Value
Access
Level
B03.07 LOC/REM Run Sel Determines action after switching
Run/Speed reference source.
00–01 00 Adv
00 Cycle Extrn Run If the run command is present at the
time when Run/Speed reference
source is switched, it requires the run
command to be removed and then
reapplied from the new source to
resume the normal operation.
01 Accep Extrn Run If the run command is present at the
time when the Run/Speed reference
source is switched, it does not require
the run command from the new source
to be removed. The normal operation
will continue.
B03.10 Allow Run at Power UP 00–01 00 Adv
00 Disabled
01 Enabled
Parameter
Code Name Function Range
Initial
Value
Access
Level
B03.15 Reference Source 2
Selection
Source from where the frequency
reference is generated.
00–04 01 Adv
00 Digital Operator Digital operator (Keypad).
01 Terminal Control circuit terminal
02 Communication Memobus Serial Communication
03 Not Used Not Used
04 Pulse Input Pulse Input (H06.01)
B03.16 Run Source 2 Selection Selects run command input source
when H01.xx = 1F.
00–03 01 Adv
00 Digital Operator Digital operator
01 Terminals Control circuit terminal.
02 Memobus
Communication
Memobus
03 Not Used Not Used