User notice
M24D Hellios
V 1.0
the temperature drops below the setpoint or the outdoor temperature drops below 5ºC.
The compressor requires a minimum time delay to start-up when disconnected or reconnected during
operation. This delay can be modified using the tC parameter.
Heating:
Heating will start-up when the indoor temperature drops below the setpoint - dHparameter - dt parameter.
Heating will cutout when the indoor temperature climbs above: setpoint - dH parameter or when the outdoor
temperature is below the Pd parameter.
Ambient control graphic based on indoor temperature.
*The air conditioning will stop automatically if the temperature drops below 5ºC.
4.5.8. Demisting, De-icing
Start the Defrost function manually by pressing .
The air conditioning and heating will activate simultaneously, in High speed ventilation mode. The air conditioning
will stop when the outdoor temperature drops below 5ºC.
To modify the fan speed, press
and then or , until the required Defrost speed is selected
The period of operation of the air flow can be defined using the td parameter. After this period, the system will
return to its previous status.
The Defrost LED will remain illuminated throughout the entire cycle. At the end of the cycle, it will flash twice.
Indicates that demisting is in
progress