167
Frequency setting by analog input (terminal 1, 2, 4)
4
PARAMETERS
Refer to the following table and set Pr. 73 and Pr. 267. ( indicates the main speed setting)
Set the voltage/current input switch referring to the table below.
AU
signal
Terminal 4 Input
Pr. 73
Setting
Terminal 2
Input
Terminal 1
Input
Compensation Input
Terminal and
Compensation Method
Polarity Reversible
OFF
0
0 to 10V 0 to 10V
Ter m in a l 1
Added compensation
No
(Indicates that a
frequency command
signal of negative
polarity is not
accepted.)
1
(initial value)
0 to to 5V 0 to 10V
2
0 to 10V 0 to 5V
3
0 to 5V 0 to 5V
4 0 to 10V
0 to 10V
Ter m in a l 2
Override
5 0 to 5V
0 to 5V
6
0 to 20mA 0 to 10V
Ter m in a l 1
Added compensation
7
0 to 20mA 0 to 5V
10
0 to 10V 0 to 10V
Yes
11
0 to 5V 0 to 10V
12
0 to 10V 0 to 5V
13
0 to 5V 0 to 5V
14 0 to 10V
0 to 10V
Ter m in a l 2
Override
15 0 to 5V
0 to 5V
16
0 to 20mA 0 to 10V
Ter m in a l 1
Added compensation
17
0 to 20mA 0 to 5V
ON
Pr. 267 setting 0
0 to 10V
Ter m in a l 1
Added compensation
No
(Indicates that a
frequency command
signal of negative
polarity is not
accepted.)
0
(initial
value)
4 to 20mA
1
(initial value)
0 to 10V
20 to 5V
30 to 5V
4 0 to 10V
Ter m in a l 2
Override
1 1 to 5V *
5 0 to 5V
6
0 to 10V
Ter m in a l 1
Added compensation
70 to 5V
10 0 to 10V
Yes
11 0 to 10V
2 2 to 10V *
12 0 to 5V
13 0 to 5V
14 0 to 10V
Ter m in a l 2
Override
15 0 to 5V
16
0 to 10V
Ter m in a l 1
Added compensation
17 0 to 5V
: Invalid
* If the input specification to terminal 4 is changed from the current input (Pr. 267 = "0") to the 0 to 5V or 0 to 10V voltage input (Pr. 267 ="1 or
2"), calibrate the input with C6. (Refer to page 172)
Terminal 2 Input
Specifications
Pr. 73 Setting Switch 2
Terminal 4 Input
Specifications
Pr. 267 Setting Switch 1
Voltage input (0 to 10V) 0, 2, 4, 10, 12, 14 OFF Voltage input (0 to 10V) 2 OFF
Voltage input (0 to 5V) 1 (initial value), 3, 5, 11, 13, 15 OFF Voltage input (0 to 5V) 1 OFF
Current input (0 to 20mA) 6, 7, 16, 17 ON Current input (0 to 20mA) 0 (initial value) ON
CAUTION
Turn the AU signal ON to make terminal 4 valid.
Match the setting of parameter and switch. A different setting may cause a fault, failure or malfunction.
The terminal 1 (frequency setting auxiliary input) signal is added to the main speed setting signal of the terminal 2 or 4.
When an override is selected, the terminal 1 or 4 is used for the main speed setting and the terminal 2 for the override signal
(50% to 150% at 0 to 5V or 0 to 10V). (When the main speed of the terminal 1 or terminal 4 is not input, compensation by the
terminal 2 is invalid.))
Use Pr. 125 (Pr. 126) (frequency setting gain) to change the maximum output frequency at input of the maximum output frequency
command voltage (current). At this time, the command voltage (current) need not be input.
Also, the acceleration/deceleration time, which is a slope up/down to the acceleration/deceleration reference frequency, is not
affected by the change in Pr. 73 setting.
When Pr. 22 Stall prevention operation level = "9999", the value of the terminal 1 is as set to the stall prevention operation level.
When Pr. 561 PTC thermistor protection level "9999", terminal 2 is not available for analog frequency command.
(
indicates an initial value.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)