13 - 26
Chapter 13 Control Sub Functions
[2] Control details
The following drawing shows the operation of the torque limit function.
[QD77MS4 operation example]
300 250
100 1500
0
0 300 300 100 150 150
1: The torque limit setting value or torque output setting value becomes effective at the PLC READY signal [Y0] rising edge
(however, after the servo turned ON.)
If the torque output setting value is "0" or larger than the torque limit setting value, the torque limit setting value will be its value.:
2: The torque limit setting value or torque output setting value becomes effective at the positioning start signal [Y10] rising edge.
If the torque output setting value is "0" or larger than the torque limit setting value, the torque limit setting value will be its value.
3: The torque chan
g
e value is cleared to "0" at the positionin
g
start si
g
nal [Y10] risin
g
ed
g
e.
Each operations
PLC READY signal [Y0]
All axis servo ON [Y1]
Torque limit setting value
(26)
Pr.17
Torque output setting
value (1552)
Cd.101
New torque value/
forward new torque value
(1525)
Cd.22
Torque limit stored value/
forward torque limit
stored value (826)
Md.35
1
1
2 2 2
3
3
0
Torque change function
switching request (1563)
Cd.112
3
Positioning start signal [Y10]
(Note): Refer to Section 3.3 for input/output signal or Chapter 5 for buffer memory address of QD77MS16.
Fig. 13.11 Torque limit function operation
[3] Precautions during control
(1) When limiting the torque at the "
Pr.17
Torque limit setting value", confirm
that "
Cd.22
New torque value/forward new torque value" or "
Cd.113
Reverse new torque value" is set to "0". If this parameter is set to a value
besides "0", the setting value will be validated, and the torque will be limited
at that value. (Refer to Section 13.5.4 "Torque change function" for details
about the "new torque value".)
(2) When the “
Pr.54
OPR torque limit value “exceeds the “
Pr.17
Torque
limit setting value”, an error occurs. (Error code: 995)
(3) When the operation is stopped by torque limiting, the droop pulse will remain
in the deviation counter. If the load torque is eliminated, operation for the
amount of droop pulses will be carried out.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-Q QD77MS and is the answer not in the manual?

Mitsubishi MELSEC-Q QD77MS Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-Q QD77MS
CategoryControl Unit
LanguageEnglish

Related product manuals