LC100 Instruction manual
4/6 Parameters
8/12 Time
Type H
H-16
Save energy mode
0-1
Parameter is used for switching on the power saving mode. In the power
saving mode after time set in parameter H-17 all the displays are switched off
and output for power saving FO-57 is switched on.
Trough relay with the power saving FO-57 it is posible to disconnect all
unnessesary power consumers.
H-17
UNLOCKING signal duration
0-25s
The parameter is the time after which power energy mode is switched on.
H-18
Output FO-058 OFF delay
0.0-3.0s
Output function FO-058 OFF delay. It is used for A3 overspeed governer.
H-19
Acceleration time (for time positioning)
0.0-20.0s
Estimated elevator acceleration time.
(time it takes the elevator to reach full speed for standstill; used only for time
positioning system)
H-20
Time for OFF FUN-58 for AMI
0-250s
Parameter for setting the additional time to hold on function FO-058 when
elevator arrive to station. Function FO-058 is switched on automaticly when
elevator start drive.