4.12 Factory - Type T
Parameter for choosing the standard for software.
1 – EN81 standard
2 – Russian standard (firefighter mode)
When in firefigihter mode open cabin doors, elevator stay with opened
doors until new call. Closing door is possible with holding door close button,
until door is not full closed if holding is interrupt, door’s automatically
reopening.
3 – Reserved
Time for starting the inverter
Time for powering the frequency inverter. Defines the time for regulator to
power up to ready state. Controlling the regulator is done through input with
function FI-226.
Time for powering the main supply contactor
Time for switching on the main supply contactor. Defines the delay to switch
on the output function FO-019. It is used for frequency regulated elevators with
evacuation. When the control cabinet is powered if the input for evacuation FI-
207 is not active output for main supply contactor (FO-019) is switched on with
delay T-03. If the input FI-207 is active then output for UPS contactor (FO-020)
is switched on with delayT-04.
Time for powering the UPS contactor
Time for switching on the UPS supply contactor. Defines the delay to switch
on the output function FO-020. It is used for frequency regulated elevators with
evacuation. When the control cabinet is powered if the input for evacuation FI-
207 is not active output for main supply contactor (FO-019) is switched on with
delay T-03. If the input FI-207 is active then output for UPS contactor (FO-020)
is switched on with delayT-04.
Time for start motor conntactors
Working time for the motor start function (FO-08).
Function is used for elevators with surveillance system to keep track for
servicing the elevators. Parameter T-06 is for setting the day in the month,
parameter T-07 is for setting the month and T-08 is for setting the year.