INPUT FUNCTIONS TABLE
Input function for switching to recall program.
Recall pushbutton up input function.
Recall pushbutton down input function.
Input function for power supply phase loss relay control.
Input function for controling the safety circuit control device used for
relevelling and preopening the doors.
Input function for elevators with short safety space. After the input is once
activated (input FI-206) elevator is blocked until reset button on the LC100-
D2 is pressed or activation of input FI-327
Input function for emergency passanger evacuation. After the input is active
elevator begins evacuation acording to the parameter A-04
Input function for motor bimetal sensor. After the input is activated function
motor fan FO-18 is switched on.
Input for fan contactor control.
Input for fire program 1. After the input is activated elevator goes to fire
program, existing calls are ignored, elevator goes to the station which is
defined in the parameter B-07. After the elevator ends with the fire program it
is blocked until input is switched off.
Input for fire program 2. After the input is activated elevator goes to fire
program, existing calls are ignored, elevator goes to the station which is
defined in the parameter B-08. After the elevator ends with the fire program it
is blocked until input is switched off.
Input for fire program 3. After the input is activated elevator goes to fire
program, existing calls are ignored, elevator goes to the station which is
defined in the parameter B-09. After the elevator ends with the fire program it
is blocked until input is switched off.
Input for fire program 4. After the input is activated elevator goes to fire
program, existing calls are ignored, elevator goes to the station which is
defined in the parameter B-17. After the elevator ends with the fire program it
is blocked until input is switched off.
Reset input for LC100-C board.
Input for out of order status of the elevator.
Input function for time relay 1. Setting the time relay is explained in
parameters type H
Input function for time relay 2. Setting the time relay is explained in
parameters type H
Input for disableing the landing calls.
Input for elevator test mode. After the input is activated elevator is in normal
drive but the landing calls are disabled and shaft light control is disabled.
Input for up travel contactor control.
Input for down travel contactor control.
Input for low speed contactor control.
Input for high speed contactor control.