81
LC100 Instruction manual
4/6 Parameters
2/12 Call processing
Type B
B-4
Program A/B side
0-1
Program A/B side
0 Cabin doors are opened according to the parameters for door side (D-02
to D-11) independently to landing call side. (ex. if in the 2nd floor has two doors
(A and B) landing call is always A side but elevator will open both doors
1 - Cabin doors are opened according to the parameters for door side (D-02
to D-11) with the side control acording to the landing call side (ex. if in the 2nd
floor has two doors (A and B) landing call on one side is „A“, and on the other
side is „B“. the elevator will open only the door on side on which the landing
call is made.
B-5
Program lift-boy
0-1
Program lift boy is the function to control elevator only with cabin comands. By
pressing the landing call blinking signalization is switched on in the cabin for
matching call. After that lift boy is processing the calls from the cabin.
0 „lift boy“ function not on
1 „lift boy“ function activated
B-6
Main landing floor
1-A1
Choosing the main floor.
In the main floor elevator with the „one way collective“ system of landing call
procesing (B-1=1) has the function for both direction collecting.
B-7
Fire stop zone 1
0-A1
Defining the floor for evacuation in case of fire program 1. Fire program 1 is
activated through the input with the function parameter FI-210.
When the fire program is activated elevator erases all existing cabin and
landing calls and switch on the cabin call to the fire stop zone 1 floor. Then
elevator goes to the fire stop tone 1 floor and opens the door. If the elevator was
driving when fire program was activated it will end current drive and then go to
fire stop floor.
B-8
Fire stop zone 2
0-A1
Defining the floor for evacuation in case of fire program 2. Fire program 2 is
activated through the input with the function parameter FI-211.
Fire program 2 has lower priority than fire program 1.
B-9
Fire stop zone 3
0-A1
Defining the floor for evacuation in case of fire program 3. Fire program 3 is
activated through the input with the function parameter FI-212.
Fire program 3 has lower priority than fire program 2 and 1