Parameter is used to set speed encoding for inspection speed 1. Parameter is
available only for frequency regulated elevators (C-01=3). Sign „ “ under a
specific letter means that in intermidiate speed board activates the outputs with
the belonging parameter.
Meaning of the letters is explained in parameter C-2.
Delay time for switching off the motor contactors
Delay for switching of the motor contactors (function FO-001 or FO-002) from
the moment when stopping comand is given (when elevator reaches the stopping
switch FI-256 or FI-257).
Time for switching on the brake contactors
Delay time for switching on the brake contactors (function FO-011) from the
moment start command is given (function FO-001 or FO-002).
Delay time for switching off the brake contactor
Delay time for switching off the brake contactor (function FO-011) from the
moment stopping command is given (when elevator reaches the stopping switch
FI-256 or FI-257).
Time for brake holding voltage
Time for low brake voltage. Function for brake holding voltage, FO-12 is
switched on parallel with function for the brake FO-11 and is on during time
defined with parameter C-12.
Working time for main drive fan
Working time for main drive fan FO-18. Function for fan FO-18 is switched on
when bimetal input signal is switched on FI-208, and it is on during time defined
with parameter C-13.
Starting time for motor pump
Starting time for motor pump for hydraulics elevators C-01=4. It defines time
for function „start pump“ FO-13.