96
LC100 Instruction manual
4/6 Parameters
5/12 Positioning
Type E
E-04
Preopening speed [imp/s]
0-100imp
Parameter is used as a speed control for preopening the doors. Speed is
measured by the number of impulses on the inductive switch (positioning type
E-01=4 or 5). If the speed is lower than one defined in the parameter E-04 then
output with the „preopening enabled“ function FO-21 is switched on.
E-05
Stopping delay in direction UP
0-2,5s
Parameter for stopping delay when driving up. When elevator reaches the
stopping magnet drive command is switched off and elevator stops. With this
parameter it is possible to extend the driving time after reaching the stopping
switch.
Parameter is used for leveling adjustment and it is active for all floors.
Leveling adjustment for each floor by itself is done by parameters for stopping F-XX.
E-06
Stopping delay in direction DOWN
0-2,5s
Parameter for stopping delay when driving down. When elevator reaches the
stopping magnet drive command is switched off and elevator stops. With this
parameter it is possible to extend the driving time after reaching the stopping
switch.
Parameter is used for leveling adjustment and it is active for all floors.
Leveling adjustment for each floor by itself is done by parameters for stopping F-XX.
E-07
Short floor distance 1-8
---
Parameter for defining short floor distances for floors 1 to 8.
Short floor means that the distance betwen two floors is shorter than the
deceleration distance.
Setting the short floors is done by putting the sign betwen the floors wich
have the short distance.
Between the floors that are set elevator is driving with slow speed.
On the example between the 3th and 4th floor and betwen 4th and 5th floor elevator will drive in slow speed.
E-08
Short floor distance 9-16
---
Parameter for defining short floor distances for floors 9 to 16.
Short floor means that the distance betwen two floors is shorter than the
deceleration distance.
Setting the short floors is done by putting the sign betwen the floors wich
have the short distance.
Between the floors that are set elevator is driving with slow speed.
On the example between the 12th and 13th floor and betwen 15th and 16th floor elevator will drive in slow
speed.
E-09,E-10,E-11
Short floor distance
---
E-09 - same as E-08 but for floors 17 to 24
E-10 - same as E-08 but for floors 15 to 32
E-11 - same as E-08 but for floors 33 to 40