99
LC100 Instruction manual
4/6 Parameters
8/12 Timers
Type H
H-03
Car light control type
1-2
Car light control type selection.
1 Standard Function for controling the cabin light FO-51 is switched off
afert time set in H-04 expired.
2 Reserved.
H-04
Working time for the car light
0-250s
Parameter for setting the working time for car light. After all conditions for
powering the light off are made this time must expire before switching the
power off.
H-05
OFF time for shaft light
0-250s
Parameter for setting the time to power off the shaft light. The shaft light is
switched on automaticly when inspection input is activated (FI-235), and it is
switched off after putting to normal drive and this time has expired.
H-06
Programable relay T1
---
Parameter for setting the time relay T1 . It is possible to set 3 type of time
relays:
1. BISTABIL Output function FO-33 changes every time on positive puls
on input function FI-216.
2. IMPULS Output function FO-33 switches of after time set in this
parameter after positive puls on input function FI-216.
3. DELAY Output function FO-33 is activated after time set in this
parameter after positive puls on input function FI-216.
Time settings: „ - „aa“-hours, „bb“ minutes, „cc“ seconds, „dd“miliseconds
H-08
Programable relay T2
---
Parameter for setting the programabile relay T2. Setting is the same as for T1, parameter H06. Input function
FI-217, output function FO-34. *if BISTABIL are sets then throught CAN message work out of order, and
B-17 parameter. (included in new firmware version 4.328.0 or higher).