10/05 AWB8230-1541GB
Holding register (word
variable)
179
1149 C101 Motor potentiometer –
reference value for motor
potentiometer after power
supply interruption
rw 00: Clear last value and use default for
PNU F001
–
01: Use saved motor potentiometer value set
with UP/DWN function through digital
inputs.
114A C102 Reset function (RST) –
response to a Reset signal
rw 00: On a rising edge the fault signal is reset and
the motor is stopped.
–
01: On a falling edge the fault signal is reset and
the motor is stopped.
02: On a rising edge the fault message is reset.
114B C103 Reserved rw – –
114C C111 Reserved
rw – –
114D C121 Reserved
rw – –
114E C122 Reserved rw – –
114F C123 Reserved rw – –
1150 C141 Logic function – select input
A
rw 00: RUN: In operation –
01: FA1: Frequency reference value reached
02: FA2: Frequency signal – output frequency
exceeds value in PNU C042 (during
acceleration ramp) or PNU C043 (during
deceleration ramp)
03: OL: Overload warning – motor current
exceeds value in PNU C041.
04: OD: PID control – reference/actual value
difference exceeds signalling threshold set
with PNU C044.
05: AL: Fault – fault/alarm signal
06: Dc: Warning – Reference value at input O
(0 to +10 V) lower than value in PNU b082
or current signal at input OI below 4 mA.
07: FBV: PID control – Actual value monitoring
(PV) signal on breach of limit values
PNU C052/C053.
08: NDc: Fault/warning dependent on
PNU C077 – communication watchdog
timer has expired: communications are
faulty.
10: ODc: Fault/warning – communication
overload or interrupted (with optional
DE51-NET-CAN, DE51-NET-DP).
1151 C142 Logic function – select input
B
rw Values a PNU C141 –
1152 C143 Logic function – select link
[LOG]
rw 00: [LOG] = A AND B –
01: [LOG] = A OR B
02: [LOG] = A XOR B
1153 C144 Digital output 11 –
deceleration time (On)
rw 0 – 100 s 0.1 [s]
Holding
register
Function
code
Name Access
rights
Value range Manipulated
variable
hex