ioLogik E2210 User’s Manual Modbus/TCP Address Mappings
B-2
Reference Address Data Type Description
00031 0x001E 1 bit CH6 DO Pulse Operate Status 0: Off 1: On
00032 0x001F 1 bit CH7 DO Pulse Operate Status 0: Off 1: On
00033 0x0020 1 bit CH0 DO Power-On Pulse Operate Status 0: Off 1: On
00034 0x0021 1 bit CH1 DO Power-On Pulse Operate Status 0: Off 1: On
00035 0x0022 1 bit CH2 DO Power-On Pulse Operate Status 0: Off 1: On
00036 0x0023 1 bit CH3 DO Power-On Pulse Operate Status 0: Off 1: On
00037 0x0024 1 bit CH4 DO Power-On Pulse Operate Status 0: Off 1: On
00038 0x0025 1 bit CH5 DO Power-On Pulse Operate Status 0: Off 1: On
00039 0x0026 1 bit CH6 DO Power-On Pulse Operate Status 0: Off 1: On
00040 0x0027 1 bit CH7 DO Power-On Pulse Operate Status 0: Off 1: On
00041 0x0028 1 bit CH0 DO Safe Pulse Operate Status 0: Off 1: On
00042 0x0029 1 bit CH1 DO Safe Pulse Operate Status 0: Off 1: On
00043 0x002A 1 bit CH2 DO Safe Pulse Operate Status 0: Off 1: On
00044 0x002B 1 bit CH3 DO Safe Pulse Operate Status 0: Off 1: On
00045 0x002C 1 bit CH4 DO Safe Pulse Operate Status 0: Off 1: On
00046 0x002D 1 bit CH5 DO Safe Pulse Operate Status 0: Off 1: On
00047 0x002E 1 bit CH6 DO Safe Pulse Operate Status 0: Off 1: On
00048 0x002F 1 bit CH7 DO Safe Pulse Operate Status 0: Off 1: On
00049 0x0030 1 bit CH0 DI Counter Status 0: Off 1: On
00050 0x0031 1 bit CH1 DI Counter Status 0: Off 1: On
00051 0x0032 1 bit CH2 DI Counter Status 0: Off 1: On
00052 0x0033 1 bit CH3 DI Counter Status 0: Off 1: On
00053 0x0034 1 bit CH4 DI Counter Status 0: Off 1: On
00054 0x0035 1 bit CH5 DI Counter Status 0: Off 1: On
00055 0x0036 1 bit CH6 DI Counter Status 0: Off 1: On
00056 0x0037 1 bit CH7 DI Counter Status 0: Off 1: On
00057 0x0038 1 bit CH8 DI Counter Status 0: Off 1: On
00058 0x0039 1 bit CH9 DI Counter Status 0: Off 1: On
00059 0x003A 1 bit CH10 DI Counter Status 0: Off 1: On
00060 0x003B 1 bit CH11 DI Counter Status 0: Off 1: On
00061 0x003C 1 bit
CH0 DI Clear Counter Value read always: 0
Write: 1: Clear counter value
0: return Illegal Data Value
00062 0x003D 1 bit
CH1 DI Clear Counter Value read always: 0
Write: 1: Clear counter value
0: return Illegal Data Value
00063 0x003E 1 bit
CH2 DI Clear Counter Value read always: 0
Write: 1: Clear counter value
0: return Illegal Data Value
00064 0x003F 1 bit
CH3 DI Clear Counter Value read always: 0
Write: 1: Clear counter value
0: return Illegal Data Value
00065 0x0040 1 bit
CH4 DI Clear Counter Value read always: 0
Write: 1: Clear counter value
0: return Illegal Data Value

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E2210 and is the answer not in the manual?

Moxa Technologies ioLogik E2210 Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E2210
CategoryI/O Systems
LanguageEnglish

Related product manuals