ioLogik E2210 User’s Manual Introduction
1-4
Serial Communication Parameters
Parity None
Data bits 8
Stop bits 1
Flow control None
Speed 1200 to 115200 bps
Protocol Modbus/RTU
Built-in RTC Yes
Digital Input
Inputs 12, source type
I/O Mode DI or Event Counter (input frequency: 100 Hz)
Dry Contact Logic 0: short to GND, Logic 1: open
Wet Contact Logic 0: 0 to 3 VDC,
Logic 1: 10 to 30 VDC (DI COM to DI)
Common type 12 points / 1 COM
Isolation 2 KV rms
Digital Output
Outputs 8, sink type
On-state voltage 24 VDC nominal
Output current rating: Max. 200 mA per channel
Optical isolation 3K VDC
Protection Over temperature shutdown: 170°C
Over current limit: 750 mA/channel (typical)
Power Requirements
Power input 24 VDC nominal, 12 to 48 VDC
Power consumption 282 mA @ 24 VDC (typical)
Field power 24 VDC nominal, up to 48 VDC
Mechanical Specifications
Wiring I/O cable max. 14 AWG
Environmental
Operating temperature -10 to 60ºC (14 to 140ºF), 5 to 95%RH
Storage temperature -40 to 85ºC (-4 to 185ºF), 5 to 95%RH
Shock IEC60068-2-27
Freefall IEC60068-2-32
Vibration IEC60068-2-6
Agency Approvals
EMI FCC Part 15, CISPR (EN55022) Class A
EMS IEC61000-4-2 (ESD), level 2/3,
IEC61000-4-3 (RS), level 2, IEC61000-4-4 (EFT), level 2,
IEC61000-4-5 (Surge), level 3, IEC61000-4-6 (CS), level 2,
IEC61000-4-8 (PM), level 1, IEC61000-4-11 (Dip)
Safety UL 508, EN61000-6-2, EN61000-6-4
Warranty
2 years