The Computer
5-98 Manual # 42-02-1P28 A3
RECALL SW/COMMAND Description:
This message is displayed on the second line of the OBD “Mode of Opera-
tion” window, only if the car is configured to go into independent service
when the car has completed the recall (initiated by the recall switches or
command).
Car actions:
None. This is informational only to indicate that the car is on independent
service due to an active recall switch or command.
Troubleshooting:
1. Check that all recall switches are deactivated.
2. Check the related Keyboard Control (KCE) option.
3. Check that the iMonitor is not sending the command and /or the com-
mand’s parameters are set per the desired operation.
RECALL DONE (210)
RECALL DONE . . . (335)
Description: Car has completed recall operation.
Troubleshooting: Check recall input.
RECALL SW: BYPASSED (271) Description: Informational. An active recall switch is bypassed due to a
higher mode of operation.
Recall Switch 1 (40)
Recall Switch 2 (41)
Recall Switch 3 (42)
Recall Switch 4 (43)
Description: Recall switch “n” has been activated. Fault-bypassed in Con-
struction.
System Verifies:
- Mode of operation = Recall Switch ‘n’
- Recall Data Type = Recall Switch ‘n’
- Recall Data, Complete is not True.
Troubleshooting:
If in error, verify no input is programmed (Config 01 > Configure Spare
Inputs) for this recall switch.
Otherwise, verify switch mechanically and electrically.
Verify state of input and input wiring.
RECALLING . . . (5) Description: Car is recalling to selected recall floor (fire service, Pretest
operation, Aux Power, Recalling switches, Floor operation, or PTI input).
Fault-bypassed in Construction/Inspection.
Troubleshooting:
If in error, verify that the assigned recall input (System IO > Programmed
Inputs) is inactive.
Verify user defined recall floor.
RESTRICTED MODE (344) Description: While the passcode remains active this message will be dis-
played on the Home screen and the car will not respond to hall calls. Please
refer to Passcode (Restricted Mode) on page 4-15.
RESYNC. RECALL (350) Description: Beginning on the day(s) and time designated by the RESYN-
CHRONIZATION DAYS and RESYNCHRONIZATION TIME parameters, when
the car has been idle for 30 seconds, a RESYNC. RECALL begins and the car
is recalled to the bottom floor. During the recall, a car or hall call will abort
the recall. Once the car is again idle, the recall is again attempted. This
cycle continues for one hour or until a successful resynchronization occurs.
Table 5.10 Touch Screen Event Listings
Event Description