Hoistway Control Equipment Installation
Manual # 42-02-1P28 A3 3-17
LS-EDGE Terminal Magnet Logic
The terminal limits from the LS-EDGE are positional back-up only. The controller uses serial
counter data to adjust speed depending on the positions of the virtual limits. The LS-EDGE
magnet logic provides a redundant means of terminal limits.
• L = LEVELING MAGNET (UNMARKED)
• T = TERMINAL MAGNET PRESENT (STRIPED OR WHITE)
• 0 = NO MAGNET PRESENT
•X = DON’T CARE
When the controller is powered up with no sensors present, DSL1 and USL1, are closed.
• DSL1 is open in the presence of terminal magnets at ULM, DZ, DLM, or SDD sensors.
• USL1 is open in the presence of terminal magnets at ULMR, DZR, DLMR, or SDU sen-
sors.
LS-EDGE Electrical Connection
Make electrical connections as shown in the job prints. Motion 2000 TS installations use the
DISC (discrete) and M-CAN connections.
Caution: Secure cables with a nylon tie wrap through the holes provided. This is VERY
IMPORTANT as it provides strain relief and prevents connector fatigue over time.
Figure 3.10 Sensor Connections
Parameter Settings
Verify the following parameter settings:
• Set the LANDING SYSTEM TYPE to LS-EDGE. (CONFIG 01 > BUILDING SETUP)
• The FLOOR STEP DOWN x and FLOOR STEP UP x (x = floor #) are already set at the fac-
tory. (CONFIG 02 > HOISTWAY SETUP)
•The FLOOR SUB STEP DOWN x and FLOOR SUB STEP Up x (x = floor #) are already set
at the factory. (CONFIG 02 > HOISTWAY SETUP)
ULM DZ DLM SDD ULMR DZR DLMR SDU
TTTTXXXX
ULM DZ DLM SDD ULMR DZR DLMR SDU
XXXXTTTT
The NEMA 4X / 12 ver-
sion provides strain
relief and sealed entry
using a gasketed
cover and special
hardware as shown
M CAN, Motion CAN, orange cable
DISC, Discrete, blue cable