Appendices
A-106
CJ2 CPU Unit Hardware User’s Manual
Precautions for Correct UsePrecautions for Correct Use
Use the special cables provided from OMRON for all connections whenever possible. If cables
are produced in-house, be sure they are wired correctly. External devices and the CPU Unit may
be damaged if general purpose (e.g., computer to modem) cables are used or if wiring is not cor-
rect.
We recommend the following wiring methods for RS-232C, especially in environment prone to noise.
Use shielded twisted-pair cable for communications cables.
Use a twisted-pair cable for each signal line and SG (signal ground) to connect the CPU Unit to a
communications partner. Also, bundle all the SG lines at the Unit and at the other device and connect
them together.
Connect the shield line of the communications cable to the hood (FG) of the RS-232C connector at
the Unit. Also, ground the protective earth (GR) terminal of the Power Supply Units on the CPU Rack
and the CJ-series Expansion Racks to a resistance of 100 or less. The following example shows
connecting SD-SG, RD-SG, RS-SG, and CS-SG for Serial Communications Mode using a twisted-
pair cable using the peripheral bus.
Note The hood (FG) is internally connected to the protective earth (GR) terminal on the Power Supply Unit
through the CPU Rack. FG can thus be connected by connecting the protective earth (GR) terminal on the
Power Supply Unit. The hood (FG) is also electrically connected to pin 1 (FG), but the connection resistance
between the shield and the FG is smaller for the hood. To reduce contact resistance between the hood (FG)
and the FG, connect the shield both to the hood (FG) and to pin 1 (FG).
A-4-4 Example of Recommended RS-232C Wiring
XM2S-0911-E
Hood
Shield
SG signal line
CPU Unit
External device
Signal
name
Pin
No.
Signal
name
SG signal lines
bundled together
Aluminum foil
2
3
4
5
9
1
SD
RD
RS
CS
SG
FG
FG
RD
SD
CS
RS
SG
FG
GR
CPU Unit
Power Supply Unit
Ground to 100
or less
Shield and GR connected
internally.
The hood will be grounded
if the GR terminal is grounded.

Table of Contents

Other manuals for Omron CJ2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2 and is the answer not in the manual?

Omron CJ2 Specifications

General IconGeneral
ModelCJ2
ManufacturerOmron
TypeProgrammable Logic Controller (PLC)
CPU UnitsMultiple models available (e.g., CJ2M, CJ2H)
Number of I/O PointsUp to 2, 560 points
Communication PortsEthernet/IP, EtherCAT, USB, Serial
ExpansionYes, via I/O Units and Special I/O Units
I/O Control MethodCyclic Scan, Interrupt
Programming LanguageLadder diagram, structured text, function block diagram, sequential function chart, instruction list
Built-in I/OAvailable on some models (e.g., CJ2M)
Ethernet PortYes, 1 port (depending on CPU Unit)
Serial PortsRS-232C, RS-422/485 (configurable)
USB PortYes (for programming and monitoring)
Operating Temperature0°C to 55°C
Storage Temperature-25 to 70°C
Humidity10 to 95% RH (non-condensing)
Vibration Resistance10 to 57 Hz, Amplitude: 0.075 mm, 57 to 150 Hz, Acceleration: 1 G, X, Y, and Z directions, 80 min each
Power Supply Voltage24 VDC or 100 to 240 VAC (depending on CPU Unit)

Related product manuals