1 Overview
1-8
CJ2 CPU Unit Hardware User’s Manual
1-3 Specifications
1-3-1 General Specifications
Item
CJ2H-
CPU64-EIP CPU65-EIP CPU66-EIP CPU67-EIP CPU68-EIP
Enclosure Mounted in a panel
Grounding Less than 100 Ω
CPU Rack Dimensions 90 mm x 65 mm x 80 mm (W x H x D)
Weight 280 g or less
Current Consumption 5 VDC, 0.82 A
Use Environment Ambient Operating Temperature 0 to 55°C
Ambient Operating Humidity 10% to 90%
Atmosphere Must be free from corrosive gases.
Ambient Storage Temperature −20 to 70°C (excluding battery)
Altitude 2,000 m or less
Pollution Degree 2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise Immunity 2 kV on power supply line (Conforms to IEC 61000-4-4.)
Overvoltage Category Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity Level Zone B
Vibration Resistance Conforms to JIS C60068-2-6.
Acceleration of 9.8 m/s
2
for 100 min in X, Y, and Z directions (10 sweeps of 10 min
each = 100 min total)
Shock Resistance Conforms to JIS C60068-2-27.
147 m/s
2
, 3 times in X, Y, and Z directions (100 m/s
2
for Relay Output Units)
Battery Life 5 years at 25°C
Model CJ1W-BAT01
Applicable Standards Conforms to cULus and EC Directives.