5-23
5 Installation
CJ2 CPU Unit Hardware User’s Manual
5-3 Wiring
5
5-3-1 Power Supply Wiring
z Crimp Terminals
The terminals on the Power Supply Unit are M4, self-raising terminals with screws.
Precautions for Correct UsePrecautions for Correct Use
Use crimp terminals for wiring.
Do not connect bare stranded wires directly to terminals.
Tighten the terminal block screws to the torque of 1.2 N·m.
Use crimp terminals (M4) having the dimensions shown below.
z Crimp Terminals for DC Power Supply
An alarm output is provided on Power Supply Units with a replacement notification function. Connect
the alarm output to a PLC's Input Unit or external LED indicator to enable notification when Power Sup-
ply Unit replacement is required.
z CJ1W-PA205C Power Supply Unit
z Output Specifications
ON (normal): Power Supply Unit replacement not required for at least 6 months.
OFF: Power Supply Unit replacement required within 6 months.
Transistor open-collector outputs
Maximum switching capacity: 30 VDC max., 50 mA max.
ON: Residual voltage of 2 V max., OFF: Leakage current of 0.1 mA max.
Alarm Output
7 mm max.
7 mm max.
AC100-240V
INPUT
NC
NC
L1
L2/N
CJ1W-PA205C
POWER
TEST
ALARM OUTPUT
DC30V, 50mA
NORMAL:ON
ALARM:OFF
L
Alarm output (replacement notification output)
ON: Power Supply Unit replacement not
required for at least 6 months.
OFF: Power Supply Unit replacement required
within 6 months.
24 VDC
power supply