5-23
5 Installation
CJ2 CPU Unit Hardware User’s Manual
5-3 Wiring
5
5-3-1 Power Supply Wiring
z Crimp Terminals
The terminals on the Power Supply Unit are M4, self-raising terminals with screws.
Precautions for Correct UsePrecautions for Correct Use
Use crimp terminals for wiring.
Do not connect bare stranded wires directly to terminals.
Tighten the terminal block screws to the torque of 1.2 N·m.
Use crimp terminals (M4) having the dimensions shown below.
z Crimp Terminals for DC Power Supply
An alarm output is provided on Power Supply Units with a replacement notification function. Connect
the alarm output to a PLC's Input Unit or external LED indicator to enable notification when Power Sup-
ply Unit replacement is required.
z CJ1W-PA205C Power Supply Unit
z Output Specifications
ON (normal): Power Supply Unit replacement not required for at least 6 months.
OFF: Power Supply Unit replacement required within 6 months.
Transistor open-collector outputs
Maximum switching capacity: 30 VDC max., 50 mA max.
ON: Residual voltage of 2 V max., OFF: Leakage current of 0.1 mA max.
Alarm Output
7 mm max.
7 mm max.
AC100-240V
INPUT
NC
NC
L1
L2/N
CJ1W-PA205C
POWER
TEST
ALARM OUTPUT
DC30V, 50mA
NORMAL:ON
ALARM:OFF
L
Alarm output (replacement notification output)
ON: Power Supply Unit replacement not
required for at least 6 months.
OFF: Power Supply Unit replacement required
within 6 months.
24 VDC
power supply

Table of Contents

Other manuals for Omron CJ2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2 and is the answer not in the manual?

Omron CJ2 Specifications

General IconGeneral
ModelCJ2
ManufacturerOmron
TypeProgrammable Logic Controller (PLC)
CPU UnitsMultiple models available (e.g., CJ2M, CJ2H)
Number of I/O PointsUp to 2, 560 points
Communication PortsEthernet/IP, EtherCAT, USB, Serial
ExpansionYes, via I/O Units and Special I/O Units
I/O Control MethodCyclic Scan, Interrupt
Programming LanguageLadder diagram, structured text, function block diagram, sequential function chart, instruction list
Built-in I/OAvailable on some models (e.g., CJ2M)
Ethernet PortYes, 1 port (depending on CPU Unit)
Serial PortsRS-232C, RS-422/485 (configurable)
USB PortYes (for programming and monitoring)
Operating Temperature0°C to 55°C
Storage Temperature-25 to 70°C
Humidity10 to 95% RH (non-condensing)
Vibration Resistance10 to 57 Hz, Amplitude: 0.075 mm, 57 to 150 Hz, Acceleration: 1 G, X, Y, and Z directions, 80 min each
Power Supply Voltage24 VDC or 100 to 240 VAC (depending on CPU Unit)

Related product manuals