5-27
5 Installation
CJ2 CPU Unit Hardware User’s Manual
5-3 Wiring
5
5-3-3 Wiring Basic I/O Units with Connectors
This section describes wiring for CJ-series Basic I/O Units with connectors (32- and 64-point Units).
Depending on the connector, the following methods are used to connect these Units to external I/O
devices.
Use an OMRON Connecting Cable (equipped with a special connector) to connect to a Terminal
Block or Relay Terminal.
Use a special connector and user-provided cable.
Precautions for Safe Use
Be sure not to apply a voltage that exceeds the input voltage for Input Units or the maximum
switching capacity for Output Units.
When the power supply has positive and negative terminals, be sure to wire them correctly.
Loads connected to Output Units may malfunction if the polarity is reversed.
Use reinforced insulation or double insulation on the DC power supply connected to DC I/O
Units when required by EC Directives (low voltage).
When connecting the connector to the I/O Unit, tighten the connector screws to a torque of
0.2 N·m.
Turn ON the power after checking the connector's wiring.
Do not pull the cable. Doing so will damage the cable.
Bending the cable too sharply can damage or break wiring in the cable.
Additional Information
CJ-series Basic I/O Units with Fujitsu connectors have the same connector pin allocations as the
C200H High-density I/O Units and CS-series I/O Units with connectors to make them compati-
ble.
For details on using OMRON Connecting Cables equipped with special connectors to connect Basic I/O
Units with connectors to OMRON Connector-Terminal Block Conversion Units or I/O Relay Terminals,
refer to A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals.
5-3-3 Wiring Basic I/O Units with Connectors
Connecting to a Connector-Terminal Block Conversion Unit or I/O
Relay Terminal

Table of Contents

Other manuals for Omron CJ2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2 and is the answer not in the manual?

Omron CJ2 Specifications

General IconGeneral
ModelCJ2
ManufacturerOmron
TypeProgrammable Logic Controller (PLC)
CPU UnitsMultiple models available (e.g., CJ2M, CJ2H)
Number of I/O PointsUp to 2, 560 points
Communication PortsEthernet/IP, EtherCAT, USB, Serial
ExpansionYes, via I/O Units and Special I/O Units
I/O Control MethodCyclic Scan, Interrupt
Programming LanguageLadder diagram, structured text, function block diagram, sequential function chart, instruction list
Built-in I/OAvailable on some models (e.g., CJ2M)
Ethernet PortYes, 1 port (depending on CPU Unit)
Serial PortsRS-232C, RS-422/485 (configurable)
USB PortYes (for programming and monitoring)
Operating Temperature0°C to 55°C
Storage Temperature-25 to 70°C
Humidity10 to 95% RH (non-condensing)
Vibration Resistance10 to 57 Hz, Amplitude: 0.075 mm, 57 to 150 Hz, Acceleration: 1 G, X, Y, and Z directions, 80 min each
Power Supply Voltage24 VDC or 100 to 240 VAC (depending on CPU Unit)