EasyManuals Logo

Omron CJ2 User Manual

Omron CJ2
353 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
2-15
2 Basic System Configuration and Devices
CJ2 CPU Unit Hardware User’s Manual
2-1 Basic System Configuration
2
2-1-4 Configuration Units
Special I/O
Units
Temperature
Control Units
4 control loops, tem-
perature- resistance
thermometer inputs,
PNP outputs
CJ1W-TC102 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
0.25 --- 150 g max.
2 control loops, tem-
perature-resistance
thermometer inputs,
NPN outputs, heater
burnout detection
CJ1W-TC103 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
0.25 --- 150 g max.
2 control loops, tem-
perature-resistance
thermometer inputs,
PNP outputs, heater
burnout detection
CJ1W-TC104 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
0.25 --- 150 g max.
Position Con-
trol Units
1 axis, pulse output;
open collector output
CJ1W-NC113 10 words 100 words 0 to 95 0.25 --- 100 g max.
2 axes, pulse out-
puts; open collector
outputs
CJ1W-NC213 10 words 100 words 0 to 95 0.25 --- 100 g max.
4 axes, pulse out-
puts; open collector
outputs
CJ1W-NC413 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
0.36 --- 150 g max.
1 axis, pulse output;
line driver output
CJ1W-NC133 10 words 100 words 0 to 95 0.25 --- 100 g max.
2 axes, pulse out-
puts; line driver out-
puts
CJ1W-NC233 10 words 100 words 0 to 95 0.25 --- 100 g max.
4 axes, pulse out-
puts; line driver out-
puts
CJ1W-NC433 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
0.36 --- 150 g max.
Space Unit
*1
CJ1W-SP001 None None --- 0.56 --- 50 g max.
ID Sensor
Units
V600-series single-
head type
CJ1W-V600C11 10 words 100 words 0 to 95 0.26 0.12 120 g max.
V600-series two-
head type
CJ1W-V600C12 20 words 200 words 0 to 94
(uses
words for
2 unit
numbers)
0.32 0.24 130 g max.
V680-series single-
head type
CJ1W-V680C11 10 words 100 words 0 to 95 0.26 0.13 120 g max.
V680-series two-
head type
CJ1W-V680C12 20 words 200 words 0 to 94 0.32 0.26 130 g max.
High-speed
Counter Unit
Two-axis pulse input,
counting rate:
500 kcps max.,
line driver compatible
CJ1W-CT021 40 words 400 words 0 to 92
(uses
words for
4 unit
numbers)
0.28 --- 100 g max.
CompoNet
Master Unit
CompoNet remote
I/O: 2,048 words, 512
bits max.
CJ1W-CRM21 10 words 100 words 0 to 95 0.40 --- 130 g max.
Compo-
Bus/S Mas-
ter Units
CompoBus/S remote
I/O, 256 bits max.
CJ1W-SRM21 10 words or
20 words
None 0 to 95 or
0 to 94
0.15 ---
66 g max.
*2
Type Name Specifications Model
Number of
words allo-
cated (CIO
2000 to CIO
2959)
Number of
words allo-
cated
(D20000 to
D29599)
Unit No.
Current consump-
tion (A)
Weight
5 VDC 24 VDC

Table of Contents

Other manuals for Omron CJ2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2 and is the answer not in the manual?

Omron CJ2 Specifications

General IconGeneral
ModelCJ2
ManufacturerOmron
TypeProgrammable Logic Controller (PLC)
CPU UnitsMultiple models available (e.g., CJ2M, CJ2H)
Number of I/O PointsUp to 2, 560 points
Communication PortsEthernet/IP, EtherCAT, USB, Serial
ExpansionYes, via I/O Units and Special I/O Units
I/O Control MethodCyclic Scan, Interrupt
Programming LanguageLadder diagram, structured text, function block diagram, sequential function chart, instruction list
Built-in I/OAvailable on some models (e.g., CJ2M)
Ethernet PortYes, 1 port (depending on CPU Unit)
Serial PortsRS-232C, RS-422/485 (configurable)
USB PortYes (for programming and monitoring)
Operating Temperature0°C to 55°C
Storage Temperature-25 to 70°C
Humidity10 to 95% RH (non-condensing)
Vibration Resistance10 to 57 Hz, Amplitude: 0.075 mm, 57 to 150 Hz, Acceleration: 1 G, X, Y, and Z directions, 80 min each
Power Supply Voltage24 VDC or 100 to 240 VAC (depending on CPU Unit)