264
Example Application Section 7-9
Unit 3 Read Data Area
(SYSWAY)
The segment information is 1 and the command group is 1.
Note The entire Unit 3 read data area is refreshed even though command group 1
is selected and only the values in DM 0240 to DM 0242 are read from the
component. (The contents of DM 0244 to DM 0250 are cleared to 0000.)
When communicating with a Temperature Controller through SYSWAY,
always allocate 11 words to the read data area even if the selected command
group limits the number of words actually read.
Unit 3 Write Data Area
(SYSWAY)
The segment information is 1 and the command group is 1.
Note It is possible to write just the target temperature by selecting command group
1.
When communicating with a Temperature Controller through SYSWAY,
Word Function
DM 0240 Response monitor area
Contains 0000 when component communications are normal.
DM 0241 Present temperature
Contains the PV in 2’s complement signed binary format.
DM 0242 Status
Contains the status when the PV was read.
DM 0243 Target temperature (See note.)
Contains the target temperature in 2’s complement signed binary format.
DM 0244 Alarm 1 SV (See note.)
Contains the alarm 1 set value in 2’s complement signed binary format.
DM 0245 Alarm 2 SV (See note.)
Contains the alarm 2 set value in 2’s complement signed binary format.
DM 0246 Proportional band (See note.)
Contains the proportional band setting in binary.
DM 0247 Reset time (See note.)
Contains the reset time setting in binary.
DM 0248 Derivative time (See note.)
Contains the derivative time setting in binary.
DM 0249 Heater current monitor (See note.)
Contains the heater’s electrical current in binary.
DM 0250 Heater current status (See note.)
Contains the status when the heater’s electrical current was read.
Word Function
DM 0260 Response monitor area
Contains 0000 when component communications are normal.
DM 0261 Target temperature
00C8 (200°C)
DM 0262 Operation command (See note.)
0000
DM 0263 Alarm 1 SV (See note.)
Set the alarm 1 set value in 2’s complement signed binary format.
DM 0264 Alarm 2 SV (See note.)
Set the alarm 2 set value in 2’s complement signed binary format.
DM 0265 Proportional band (See note.)
Set the proportional band setting in binary.
DM 0266 Reset time (See note.)
Set the reset time setting in binary.
DM 0267 Derivative time (See note.)
Set the derivative time setting in binary.
DM 0268 Heater burnout detection value (See note.)
Set the heater burnout detection value in binary.