6-4
n109 Torque Compensation Limit Register 016D
Hex
Changes during
operation
No
Setting
range
0 to 250 (%) Unit of
setting
1% Default setting 150
Note 1. The Inverter in torque compensation control limits the torque at a current 1.5
times larger than the set value.
Note 2. This parameter is enabled only when the Inverter is in vector control.
H Adjusting the Torque and Response through the V/f Pattern
(n011 through n017)
·The Inverter in vector control uses the V/f pattern as the reference value of the output
voltage. Therefore, by adjusting the V/f pattern the output torque and response are
adjusted.
·If the application requires hightorque, adjust the V/f patternso that theoutput voltage
at the required frequency will be high. Furthermore, energy-saving effects can be
expectedbydecreasingtheoutput voltage values in thefrequencyrangeswherehigh
torque is not required.
n011 Maximum Frequency
(FMAX)
Register 010B
Hex
Changes during
operation
No
Setting
range
50.0 to 400.0 (Hz) Unit of
setting
0.1 Hz Default setting 60.0
n012 Maximum Voltage (VMAX) Register 010C
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 (0.1 to 510.0) (V) Unit of
setting
0.1 V Default setting 200.0
(400.0)
n013 Maximum Voltage
Frequency (FA)
Register 010D
Hex
Changes during
operation
No
Setting
range
0.2 to 400.0 (Hz) Unit of
setting
0.1 Hz Default setting 60.0
n014 Middle Output Frequency
(FB)
Register 010E
Hex
Changes during
operation
No
Setting
range
0.1 to 399.9 (Hz) Unit of
setting
0.1 Hz Default setting 1.5
n015 Middle Output Frequency
Voltage (VC)
Register 010F
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 (0.1 to 510.0) (V) Unit of
setting
0.1 V Default setting 11.0
(22.0)
Advanced Operation Chapter 6