6-5
n016 Minimum Output Frequency
(FMIN)
Register 0110
Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (Hz) Unit of
setting
0.1 Hz Default setting 1.5
n017 Minimum Output Frequency
Voltage (VMIN)
Register 0111 Hex Changes during
operation
No
Setting
range
0.1 to 50.0 (0.1 to 100.0) (V) Unit of
setting
0.1 V Default setting 4.3
(8.6)
Note Figures in brackets are for 400-V Inverter models.
Output voltage (V)
Note 1. Set theparameters sothat thefol-
lowing condition will be satisfied.
n016 n014 < n013 n011
Note 2. The value set in n015 will be
ignored if parameters n016 and
n014 are the same in value.
Frequency (Hz)
·The vertical-axis load or the load with high viscous friction may require high torque at
low speed. If the torque is insufficient at low speed, increase the voltage in the low-
speedrangeby1V,providedthatnooverload(OL1orOL2)isdetected.Ifanoverload
is detected, decrease the setvaluesorconsider the use ofan Invertermodel or motor
with a higher capacity.
·Therequiredtorqueoffan or pump control increasesinproportiontothesquare ofthe
speed. By setting a quadratic V/f pattern to increase the voltage in the low-speed
range, the power consumption of the system will increase.
Advanced Operation Chapter 6