10-15
Para
me-
ter
No.
Ref-
er-
ence
page
Chan-
ges dur-
ing
opera-
tion
Defaul
t set-
ting
Unit
of
set-
ting
Set-
ting
range
DescriptionNameReg-
ister
No.
13 Inverter
ready
ON: Inverter ready to
operate (with no fault
detected)
14 Fault retry ON: Fault retry
15 UV in prog-
ress
ON: Undervoltage
being monitored
16 Rotating in
reverse
direction
ON: Rotating in
reverse direction
17 Speed
search in
progress
ON: Speed search in
progress
18 Commu-
nications
output
ON: Turns communica-
tions output 1 ON.
19 PID feed-
back loss
ON: PID feedback loss
enabled.
20
(see
note)
Frequency
reference
loss
ON: Frequency refer-
ence lost (when fre-
quency reference loss
detection in n064 is en-
abled, and either ana-
log input or pulse train
input is set for frequen-
cy reference selection
in n004)
21
(see
note)
Inverter
overheating
warning
oH3
ON: Inverter overheat-
ing warning (ON when
the multi-function input
Inverter overheating
warning signal is being
input, i.e., when 0H3 is
flashing.)
n060 013C Frequency
reference
gain
Used to the input characteristics of analog fre-
quency references.
Gain: The frequency of maximum analog input
(
1
0
V
o
r
2
0
m
A
)
i
n
p
e
r
c
e
n
t
a
g
e
b
a
s
e
d
o
n
t
h
e
m
a
x
i
m
u
m
f
r
e
q
u
e
n
c
y
a
s
1
0
0
%
.
0 to
255
1% 100 Yes 5-14
n061 013D Frequency
reference
bias
(
1
0
V
o
r
2
0
m
A
)
i
n
p
e
r
c
e
n
t
a
g
e
b
a
s
e
d
o
n
t
h
e
maximum frequency as 100%.
Bias: The frequency of minimum analog input (0
V or 0 or 4 mA) in percentage based on the
maximum frequency as 100%.
--100
to 100
1% 0 Yes 5-14
n062 013E Analog fre-
quency ref-
erence fil-
ter time
Used to set the digital filter with a first-order lag
for analog frequency references to be input.
0.00
to
2.00
0.01 s 0.10 No 5-15
n063 --- Not used --- --- --- --- --- ---
Note Frequencyreferenceloss(settingvalue:20)andinverteroverheatingwarning(settingvalue:21)
can be set for 5.5-kW and 7.5-kW Inverters only.
List of Parameters Chapter 10