maximum frequency as 100%.
Bias:Set the frequency of minimum analog
input (0 V) in percentage based on the
maximum frequency as 100%.
--100
to 100
1% 0 Yes NO TAG
n073 0149 Multi-func-
tion analog
current
input filter
time con-
stant
Set a primary delay digital filter for multi-function
analog current input.0.00 to 2.00
0.00
to
2.00
0.01 s 0.10 Yes NO TAG
n074 014A Pulse train
frequency
reference
gain
Set the input characteristics of pulse train input.
Gain:Set the gain in percentage based on the
maximum frequency of the pulse train
Bias:Set the bias in percentage for frequency
reference input at 0-Hz pulse train input
based on the maximum frequency as
100%.
--100
to 100
1% 0 Yes 5--24
n076 014C Pulse train
frequency
reference
input filter
time
constant
Sets the pulse train input’s primary-delay digital
filter for frequency reference.
0.00
to
2.00
0.01 s 0.10 Yes 5--25
n077 014D Multi--func-
tion analog
input termi-
nal func-
tion selec-
tion
Selects the function allocated to the multi-func-
tion analog input terminal.
0: Disable multi-function analog input function.
1: Auxiliary frequency reference
2: Frequency gain
3: Frequency bias
4: Output voltage bias
Note: When setting “3,” also set the standard
value for the bias in n079.
0 to 4 1 0 No 5--15
n078 014E Multi--func-
tion analog
input termi-
nal selec-
tion
Selects whether voltage input or current input is
to be used.
0: Enable multi-function analog voltage input
(and disable current input).
1: Enable multi-function analog current input
(and disable voltage input).
0,1 1 0 No 5--15
n079 014F Multi-func-
tion input
frequency
bias
When “3” is set for n077, set the standard value
for the bias as a percentage, taking the maxi-
mum frequency as 100%.
0 to
50
1% 10 No 5--15
List of Parameters Chapter 10