Loading...
2-45
H Conforming to LVD
·Always connect the Inverter and power supply via a molded case circuit breaker
(MCCB)suitabletotheInverterforprotectingtheInverterfromdamagethatmayresult
from short-circuiting.
·Use one MCCB per Inverter.
·Select a suitable MCCB from the following table.
200-V Models
Inverter MCCB (Mitsubishi Electric)
Model 3G3MV- Type Rated current (A)
A2001
NF30
5
A2002
N
F
3
0
5
A2004 5
A2007 10
A2015 20
A2022 20
A2040 30
A2055 50
A2075 60
AB001
NF30
5
AB002
N
F
3
0
5
AB004 10
AB007 20
AB015 20
AB022 40
AB040 50
400-V Models
Inverter MCCB (Mitsubishi Electric)
Model 3G3MV- Type Rated current (A)
A4002
NF30
5
A4004
N
F
3
0
5
A4007 5
A4015 10
A4022 10
A4030 20
A4040 20
A4055 30
A4075 30
Design Chapter 2

Table of Contents

Other manuals for Omron SYSDRIVE 3G3MV

Related product manuals