I/O Memory Allocation Section 9-3
204
CS/CJ-series PLC CX-Simulator
Item
Settings Function Settings Function
Instruction Error Op-
eration
0: Continue
1: Stop
Default: 0
This setting determines whether
instruction errors (instruction
processing errors (ER) and illegal
access errors (AER)) are treated
as non-fatal or fatal errors. When
this setting is set to 1, CPU Unit
operation will be stopped if the
ER or AER Flags is turned ON
(even when the AER Flag is
turned ON for an in direct DM/EM
BCD error).
Related Flags: A29508 (Instruc-
tion Processing Error Flag)
A29509 (Indirect DM/EM BCD
Error Flag)
A29510 (Illegal Access Error
Flag)
Same as
CS/CJ-series
PLC.
Minimum Cycle Time 0001 to 7D00:
1 to 32,000 ms
(1-ms units)
Default: 0000
(No minimum)
Set to 0001 to 7D00 to specify a
minimum cycle time. If the cycle
time is less than this setting, it will
be extended until this time
passes. Leave this setting at
0000 for a variable cycle time.
Same as
CS/CJ-series
PLC.
Enable
Watch Cy-
cle Time
Setting
0: Default
1: Bits 0 to 14
Default: 0
Set to 1 to enable the Watch
Cycle Time Setting in bits 0 to 14.
Leave this setting at 0 for a
maximum cycle time of 1 s.
Same as
CS/CJ-series
PLC.
Watch
Cycle
Time
Watch Cy-
cle Time
Setting
001 to FA0: 10 to
40,000 ms
(10-ms units)
Default: 001 (1 s)
This setting is valid only when bit
15 of 209 is set to 1. The Cycle
Time Too Long Flag (A40108) will
be turned ON if the cycle time
exceeds this setting.
Same as
CS/CJ-series
PLC.
Enable
Fixed Ser-
vicing Time
0: Default*
1: Bits 0 to 7
Default: 0
Set to 1 to enable the fixed pe-
ripheral servicing time in bits 0 to
7.
*Default: 4% of the cycle time
Not used. Fixed
Periph-
eral Ser-
vicing
Time
Fixed Ser-
vicing Time
00 to FF:
0.0 to 25.5 ms
(0.1-ms units)
Default: 00
This setting is valid only when bit
15 of 218 is set to 1.
Not used.
Power OFF Interrupt
Task
0: Disabled
1: Enabled
Default: 0
When this setting is set to 1, the
power OFF interrupt task will be
executed when power is inter-
rupted.
Same as
CS/CJ-series
PLC.
Power OFF Detection
Delay Time
00 to 0A:
0 to 10 ms (1-ms
units)
Default: 00
This setting determines how
much of a delay there will be from
the detection of a power interrup-
tion (approximately 10 to
25 ms after the power supply
voltage drops below 85% of the
rated value) to the confirmation of
a power interruption. The de-fault
setting is 0 ms.
Not used.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron WS02-SIMC1-E - V1.9 REV 02-2009 and is the answer not in the manual?

Omron WS02-SIMC1-E - V1.9 REV 02-2009 Specifications

General IconGeneral
BrandOmron
ModelWS02-SIMC1-E - V1.9 REV 02-2009
CategorySoftware
LanguageEnglish

Related product manuals