I/O Memory Allocation Section 9-3
210
Address CS/CJ-series PLC CX-Simulator
Words Bits
Name
Function Settings Function Settings
A29508 Instruction
Processing
Error Flag
This flag and the Error Flag (ER)
will be turned ON when an in-
struction processing error has
occurred and the PLC Setup has
been set to stop operation for an
instruction error. CPU Unit op-
eration will stop and the
ERR/ALM indicator will light when
this flag goes ON.
(The task number where the error
occurred will be stored in A294
and the program address will be
stored in A298 and A299.)
1: Error
Flag
ON
0: Error
Flag
OFF
Same as
CS/CJ-series
PLC.
A295
A29509 Indirect
DM/EM
BCD Error
Flag
This flag and the Access Error
Flag (AER) will be turned ON
when an indirect DM/EM BCD
error has occurred and the PLC
Setup has been set to stop op-
eration an indirect DM/EM BCD
error. (This error occurs when the
content of an indirectly addressed
DM or EM word is not BCD al-
though BCD mode has been
selected.) CPU Unit operation will
stop and the ERR/ ALM indicator
will light when this flag goes ON.
(The task number where the error
occurred will be stored in A294
and the program address will be
stored in A298 and A299.)
1: Not BCD
0: Normal
Same as
CS/CJ-series
PLC.