V–37
3) System address setting (Level 2)
Rejection conditions : Not accepted during indoor operation
Setting start operation method : Press the SET (S007) key for one second.
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
Example:

: When pressing the UP (S005) key

: When pressing the DOWN (S006) key
Setting con rm operation method : After entering the setting start operation or setting change operation
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
Setting cancel operation method : Press the HOME (S004) key for one second before con rming setting.
Setting range : 01 to 31
4) Number of connecting indoor units setting (Level 2)
Rejection conditions : Not accepted during indoor operation
Setting start operation method : Press the SET (S007) key for one second.
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
Example:

: When pressing the UP (S005) key

: When pressing the DOWN (S006) key
Setting con rm operation method : After entering the setting start operation or setting change operation
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
Setting cancel operation method : Press the HOME (S004) key for one second before con rming setting.
Setting range : 00
Not set
01 to 48
Number of indoor unit connected in same system 1 to 48 units*
(*) The number of indoor units that can be connected is restricted separately by each model.
5) Gas type setting (Level 2)
Rejection conditions : Not accepted during indoor operation
Setting start operation method : Press the SET (S007) key for one second.
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
Example:

: When pressing the UP (S005) key

: When pressing the DOWN (S006) key
Setting con rm operation method : After entering the setting start operation or setting change operation
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
Setting cancel operation method : Press the HOME (S004) key for one second before con rming setting.
Setting range : 00 to 0F
0 Propane G31

1 —

2 Natural gas G20

3 Natural gas G25

4

GHPtroubleshooting.indbV‒37GHPtroubleshooting.indbV‒37 2012/11/2611:20:212012/11/2611:20:21