V–38
6) Refrigerant setting (Level 2)
Rejection conditions : Not accepted during indoor operation
Setting start operation method : Press the SET (S007) key for one second.
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
Example:
: When pressing the UP (S005) key
: When pressing the DOWN (S006) key
Setting confi rm operation method : After entering the setting start operation or setting change operation
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
Setting cancel operation method : Press the HOME (S004) key for one second before confi rming setting.
Setting range : 00 to 02
0Not set
1Normal
2• •
7) Generator setting (Level 2)
Rejection conditions : Not accepted during indoor operation
Setting start operation method : Press the SET (S007) key for one second.
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
Example:
: When pressing the UP (S005) key
: When pressing the DOWN (S006) key
Setting confi rm operation method : After entering the setting start operation or setting change operation
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
Setting cancel operation method : Press the HOME (S004) key for one second before confi rming setting.
Setting range : 00 to 03
0Not set
1• •
2• •
3 No generator
GHPtroubleshooting.indbV‒38GHPtroubleshooting.indbV‒38 2012/11/2611:20:222012/11/2611:20:22