V–41
14) Tube connection confi rmation (Level 2) <Cannot be set if not W MULTI>
Rejection conditions : Indoor unit operation in progress, cooling automatic addressing in
progress
Setting start operation method : Push the SET (S005) key for 1 second.
(Forced / error LED light)
Setting change operation method : Automatic completion. Press the SET (S005) key for one second when
turning off.
(Forced / error LED off)
15) Heating automatic address setting (Level 2)
Rejection conditions : Not accepted during indoor operation
Setting start operation method : Press the SET (S007) key for one second.
(TEST/WARNING LED light)
Setting change operation method : Automatic completion. Press the SET (S007) key for one second when
turning off.
(TEST/WARNING LED off)
Automatic address setting status is successively displayed as shown below.
The meaning of the numbers is as follows.
0: Automatic address start setup
1: Indoor unit automatic address setup wait
2: Engine operation in progress
3: Indoor unit checking in progress
4: Address setting in progress
5: Setting complete
16) Cooling automatic address setting (Level 2)
Rejection conditions : Not accepted during indoor operation
Setting start operation method : Press the SET (S007) key for one second.
(TEST/WARNING LED light)
Setting change operation method : Automatic completion. Press the SET (S007) key for one second when
turning off.
(TEST/WARNING LED off)
Automatic address setting status is successively displayed as shown below.
The meaning of the numbers is as follows.
0: Automatic address start setup
1: Indoor unit automatic address setup wait
2: Engine operation in progress
3: Indoor unit checking in progress
4: Address setting in progress
5: Setting complete