PLX32-EIP-MBTCP-UA ♦ Multi-Protocol Gateway OPC UA Server
User Manual
ProSoft Technology, Inc. Page 139 of 156
March 8, 2018
6 The new variable is now displayed in the Variables tab.
In the example above, the new tags (MyTag_001, MyTag_002 and
MyTag_003) occupy three 16-bit words, starting at PLX32-EIP-MBTCP-
UA module memory 10. The EIP and MBTCP drivers can then access
these tags.
7 When ready, save the configuration by clicking the SAVE button.
PSW-UACM does not perform a complete validation of tag configuration settings.
If the same memory area is assigned to more than one variable, all variable
configurations will fail to load upon OPC UA Server reboot. This error is reported
in the Variables Load Result field of the Status tab.