EasyManua.ls Logo

ProSoft PLX32-EIP-MBTCP-UA - 5.2.2 Configuring EIP Class 1 Connection

ProSoft PLX32-EIP-MBTCP-UA
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EIP Protocol PLX32-EIP-MBTCP-UA Multi-Protocol Gateway
User Manual
Page 48 of 156 ProSoft Technology, Inc.
March 8, 2018
5.2.2 Configuring EIP Class 1 Connection
Use the EIP Class 1 Connection in ProSoft Configuration Builder when the
gateway acts as an EIP adapter transferring data to and from a PLC (the EIP
scanner) using a direct I/O connection. Direct I/O connections can transfer large
amounts of data quickly.
The PLX32-EIP-MBTCP-UA can handle up to eight I/O connections (depending
on the model), each with 248 words of input data and 248 words of output data.
Adding the Gateway to RSLogix5000 v.20
1 Start Rockwell Automation RSLinx and browse to the PLX32-EIP-MBTCP-
UA.
2 Right-click the gateway and then choose UPLOAD EDS FROM DEVICE.
Note: RSLogix5000 may need to be restarted in order to complete the EDS installation.
3 After you restart RSLogix 5000, open the desired RSLogix 5000 project.
4 In the Controller Organizer, right-click the EtherNet/IP bridge in the I/O tree
and choose NEW MODULE.

Table of Contents