EasyManua.ls Logo

ProSoft PLX32-EIP-MBTCP-UA - 5.2 EIP Configuration; 5.2.1 Configuring EIP Class 3 Server

ProSoft PLX32-EIP-MBTCP-UA
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PLX32-EIP-MBTCP-UA Multi-Protocol Gateway EIP Protocol
User Manual
ProSoft Technology, Inc. Page 45 of 156
March 8, 2018
5.2 EIP Configuration
5.2.1 Configuring EIP Class 3 Server
Use the EIP Class 3 Server connection in ProSoft Configuration Builder when the
gateway is acting as a server (slave) device responding to message instructions
initiated from a client (master) device such as an HMI, DCS, PLC, or PAC.
To set the server file size in PCB
1 In ProSoft Configuration Builder, click the [+] next to the gateway, then click
the [+] next to EIP Class 3 Server.
2 Double-click the second EIP Class 3 Server to display the Edit - EIP Class 3
Server dialog box.
3 Select the SERVER FILE SIZE (100 or 1000).
o For a value of 100, the registers are from N10:0 to N10:99.
o For a value of 1000, the valid registers are from N10:0 to N10:999.
Accessing the Gateway’s Internal Memory
The following table refers to the user data area in the gateway's memory:
Data Type
Tag Name
Length of Each Element in
CIP Message
Array Range for 4000
Element Database
BOOL
BOOLData[ ]
1
0 to 63999
Bit Array
BITAData[ ]
4
0 to 1999
SINT
SINTData[ ]
1
0 to 7999
INT
INT_Data[ ]
2
0 to 3999
DINT
DINTData[ ]
4
0 to 1999
REAL
REALData[ ]
4
0 to 1999

Table of Contents