The Advanced tab contains OPC UA operational parameter names, descriptions,
and adjustable values.
Name
Value
Description
MaxBrowseContinuationPoints
1 to 100
Maximum number of continuation points supported by
the browse service.
MaxArrayLength
1 to 1000
Maximum array length supported by the server.
MaxStringLength
10 to 4096
Maximum UTF8 string length supported by the server.
Enforce
True / False
Set to TRUE to enforce limits. Enforcing limits protect
against out of memory conditions but may affect
interoperability with clients that do not observe these
values.
MaxNodesPerRead
1 to 500
Maximum nodes to read in a Read service call.
MaxNodesPerWrite
1 to 500
Maximum number of nodes per Write service call.
MaxNodesPerMethodCall
1 to 10
Maximum number of nodes per Call service.
MaxNodesPerBrowse
1 to 100
Maximum number of nodes per Browse service call.
MaxNodesPerTranslateBrowsePaths
ToNodeIds
1 to 500
Maximum nodes per translate browse paths to node
ID’s service call.