OPC UA Server PLX32-EIP-MBTCP-UA Multi-Protocol Gateway
User Manual
Page 142 of 156 ProSoft Technology, Inc.
March 8, 2018
MaxNotificationRetransmissionQueue
Size
1 to 100
Maximum retransmission queue size.
MaxPublishRequestsPerSession
1 to 10
Maximum publish request per session.
MaxBrowseRefsPerNode
1 to 10000
When the server responds to a browse request, it can
limit the number of references included in the response
and prompt the client to make another service call to get
further references. This allows the server to limit the size
of browse response messages and also slows down the
browse process as more messages are required.
MaxMonitoredItems
1 to 100000
Maximum number of monitored items that the server
can support across all sessions.
MaxMonItemQueueSize
1 to 100
Maximum sample queue length for monitored items.
Where a client is only interested in the latest live data
value, the sample queue length can be set to 1. Where
a client may be interested in logging all values and/or
sampling monitored items at a slower rate than the
containing subscription reports results, this value may
be set to greater than 1.
PercentDeadbandDisable
True / False
To enable/disable monitored item percent dead band
filtering for all variables.
PercentDeadbandFloatingPoint
Disable
True / False
To enable/disable monitored item percent dead band
filtering for all floating point variables.
PercentDeadbandDoubleDisable
True / False
To enable/disable monitored item percent dead band
filtering for all double precision floating point variables.
PercentDeadbandDoubleVectors
Disable
True / False
To enable/disable monitored item percent dead band
filtering for all double precision floating point vector
variables.
UseSinglePrecisionFloatForAllFilter
Operations
True / False
To enable/disable single precision float for all filter
operation.
MinPublishingIntervalInMs
1 to 60000
Minimum acceptable value for subscription publishing
intervals.
MinSamplingIntervalInMs
10 to 60000
Minimum acceptable value for sampling intervals.
SendApplicationInstanceCertificate
ForSecurityPolicyNone
True / False
Set to true to send the application instance certificate in
the GetEndpoints service call result for endpoints with
security policy None.
SuppressCertificateExpired
True / False
Ignore expiration date of the certificate at certificate
validation.
SuppressUriMismatch
True / False
Ignore mismatch between URI of the client application,
defined in its certificate, and Application URI defined in
its Application Description.
SuppressRevocationStatusUnknown
True / False
Ignore CRLs at certificate validation.
CheckRevocationStatusOffline
True / False
Check CRLs located in file system at certificate
valdiation.
PortNumber
0 to 65000
TCP port number of server's endpoint.