EasyManuals Logo

Pulsar Ultra 4 User Manual

Pulsar Ultra 4
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
ULTRA 4 INSTRUCTION MANUAL
124
OPTION
DESCRIPTION
SETPOINTS
6 = In bounds
Relay goes “ON” if value is
inside the zone between
the two setpoints.
7 = Out of bounds
Relay goes “ON” if value is
outside the zone between
the two setpoints.
To set figures in % press the hotkey to show and enter % figure,
relative to empty level.
Important Notice
Setpoints are entered in values according to the function selected.
Level - entered in Measurement Units (P104) or % of span as referenced
to Empty Level.
Rate of Change - entered in Display Units per minute or % of span per
minute. For an alarm on an increasing level enter setpoints as a positive
value, for an alarm on a decreasing level enter setpoints as a negative
value.
Temperature - entered in ºC.
See the appropriate alarm function, table (P2n1) for further information.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar Ultra 4 and is the answer not in the manual?

Pulsar Ultra 4 Specifications

General IconGeneral
BrandPulsar
ModelUltra 4
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals