PULSAR MEASUREMENT
135
Trace Log Setup
Diagnostic echo traces can be periodically stored to the SD card for future
play back and analysis using Pulsar PC Suite software. A trace can be stored
at a standard time Interval, and at a faster interval when certain diagnostic
values exceed defined setpoints.
P917 Trace Log Enable
Turns the ability to log echo traces on or off.
P918 Normal Interval
This parameter sets the trace logging interval that a log is sampled from the
unit (in minutes) and stored on to the SD card. Default = 5 minutes
P919 Fault Interval
This parameter sets the trace logging interval when the diagnostic values
meet or exceed the setpoints defined in the following parameters P961-
P968. Default = 0.5 minutes
P961 LOE
Log traces when Loss of Echo (LOE) is detected. Default = 0 (No)
P962 Xdr Fault
Log traces when Transducer Fault is detected. Default = 0 (No)
P963 Failed Safe
Log traces when Failed Safe condition is detected. Default = 0 (No)
P964 Min Signal
Log traces when the signal strength is below this value. Default = -9999
mV
P965 Max Noise
Log traces when Avg. noise exceeds this value. Default = 9999 mV
P966 Min Temp
Log traces when measured temperature is below this value. Default = -
100
°
C
P967 Max Temp
Log traces when measured temperature exceeds this value. Default = 100
°
C