“Prg” Menu parameters list:
“Prg” Menu parameters list: 1 - 2
Menù
label
Par Label Description
U.
m.
Range
Default KCTR PW
Address
min max
USYS
200 SEtC Room set point in cooling mode (Comfort temperature) °C 15 30 24 X 16413
201 AttC
Attenuation value on Room set point in cooling mode
°C 1 10 6 X 16415
202 SEtH Room set point in heating mode (Comfort temperature) °C 5 30 20 X 16414
203 AttH Attenuation value on Room set point in heating mode °C 1 10 4 X 16416
204 C-A
Comfort/Attenuation conditions change:
On: Change comfort / Attenuation bands
Off: Time Zones of Comfort / Attenuation disabled (manual override)
- Off On Off X 16417
205 StC
Comfort conditions period start:
Time of day at which the transition is forced to the conditions of Time
of day at which the transition is forced to the conditions of Comfort
h:
min
00:00 EnC 08:00 X 16466
206 EnC
Comfort conditions period end:
Time of day in which it is forced passage conditions Attenuation
h:
min
StC 23:59 21:00 X 16467
207 diFF
Differential on Room temperature set point
Differential on the set temperature in heating / cooling, with which you
start the heat pump
°C 1 5 1 S 16418
208
SAMb
Active room set point °C - -
Read
value
8984
209 tHEr
Voltage output state Room Termostat (clamp C-D):
2Q$PELHQWWHPSHUDWXUHLVQRWVDWLV¿HG9EHWZHHQWHUPLQDOV&1
2II$PELHQWVDWLV¿HG9EHWZHHQWHUPLQDOV'1
-OnOff
Read
value
8986
210 E1Mn
Winter climatic curve, minimum external environment set temperature
°C -20 5 -5 S 16419
211 E1MA
Winter climatic curve, maximum external environment set
temperature
°C 10 40 20 S 16420
212 t1Mn
Winter climatic curve (radiant), minimum outlet water temperature set
°C 10 60 22 S 16421
213 t1MA
Winter climatic curve (radiant), maximum outlet water temperature set
°C 20 60 45 S 16422
214 ty1
:LQWHUKHDWLQJFXUYHUDGLDWLQJG\QDPLFFRPSHQVDWLRQFRHI¿FLHQW
Multiplier of the difference, between the set room temperature, and
the measured one, that represents the dynamic compensation of the
temperature curve winter. If the KCTR is not connected, or in case of
alarm AMBT, such compensation is not active
- 0 9 0 S 16423
215 t2Mn
Winter heating curve (fan coils), set outlet water temperature
minimum (active when remote contact "Set point 2" closed)
°C 20 60 45 S 16424
216 t2MA
Winter heating curve (fan coils), set outlet water temperature
maximum (active when remote contact "Set point 2" closed)
°C 10 60 45 S 16425
217 E3Mn Heating curve summer, set minimum outdoor temperature °C 20 40 23 S 16426
218 E3MA Heating curve summer, set the maximum external temperature °C 20 40 32 S 16427
219 t3Mn
Summer temperature curve (radiant), set outlet water temperature
minimum
°C 5 25 15 S 16428
220 t3MA
Summer temperature curve (radiant), set outlet water temperature
maximum
°C 5 25 22 S 16429
221 dy3
Summer temperature curve (radiating), dynamic compensation
FRHI¿FLHQW
Multiplier of the difference, between the set room temperature, and
the measured one, that represents the dynamic compensation of the
temperature curve winter. If the KCTR is not connected, or in case of
alarm AMBT, such compensation is not active
- 0 9 0 S 16430
222 t4Mn
Summer temperature curve (fan coils), set outlet water temperature
minimum (active when remote contact "Set point 2" closed)
°C 5 25 7 S 16431
223 t4Ma
Summer temperature curve (fan coils), set outlet water temperature
maximum (active when remote contact "Set point 2" closed)
°C 5 25 7 S 16432
224 tMa Maximum temperature hot water radiant plant °C 10 60 45 16433
X=Parameter also available on KCTR
S = Password service (48)
73