“Prg” Menu parameters list 2-2
Men label Par Label Description U. m.
Range
Default KCTR PW
Address
min max
AFR
241 AFEn
Frost protection mode:
- On: Frost protection by USER INTERFACE. The internal protection
must be disabled to PdC (PCB DISPLAY switch 1 OFF)
- Off: Frost protection from PdC controller (PCB DISPLAY switch 1
ON)
- On Off Off S 16443
242 AFSU
Water temperature (par. 109/111) below which there is the
LQWHUYHQWLRQRIWKH¿UVWOHYHORIIURVWSURWHFWLRQ3XPSDFWLYH
°C 2 -10 2 S 16444
243 AFSA
External air temperature (par. 108) under which you have the
LQWHUYHQWLRQRIWKH¿UVWOHYHORIIURVWSURWHFWLRQ3XPSDFWLYH
°C 2 -10 1 S 16445
244 AF2U
Water temperature (par. 109/111) below which there is the
intervention of the second level of frost protection (water heating by
PdC and / or additional generator)
°C 1 -15 -1 S 16384
245 diFA
Frost protection, differential
Differential applied at temperatures above set (AFSA, AFSU, AF2U),
beyond which disables the respective levels of protection
°C 1 15 5 S 16446
246 AFtU
Water temperature, the output from the heat pump, request the
intervention of the second level of frost protection
°C 5 30 5 S 16447
P1
247 St1
+32Q2IIWLPHUSUR¿OHVWDUW¿UVW2QSHULRG
7LPHZKHQIRUWKH¿UVWWLPHFKDQJHKDSSHQVIURP2IIWR2QLQ
SUR¿OH
h:
min
00:00 En1 08:00 X 16452
248 En1
+32Q2IIWLPHUSUR¿OHHQG¿UVW2QSHULRG
7LPHZKHQIRUWKH¿UVWWLPHFKDQJHKDSSHQVIURP2QWR2IILQ
SUR¿OH
h:
min
St1 St2 12:00 X 16453
249 St2
+32Q2IIWLPHUSUR¿OHVWDUWVHFRQG2QSHULRG
Time when, for the second time, change happens from Off to On, in
SUR¿OH
h:
min
En1 En2 14:00 X 16454
250 En2
+32Q2IIWLPHUSUR¿OHHQGVHFRQG2QSHULRG
Time when, for the second time, change happens from On to Off, in
SUR¿OH
h:
min
St2 23:59 17:00 X 16455
P2
251 St
+32Q2IIWLPHUSUR¿OHVWDUW2QSHULRG
7LPHZKHQFKDQJHKDSSHQVIURP2IIWR2QLQSUR¿OH
h:
min
00:00 En 08:00 X 16456
252 En
+32Q2IIWLPHUSUR¿OHHQG2QSHULRG
7LPHZKHQIRUWKH¿UVWWLPHFKDQJHKDSSHQVIURP2QWR2IILQ
SUR¿OH
h:
min
St 23:59 17:00 X 16457
dAYS
253 MOn
$VVLJQPHQWRIWKHIRXUSUR¿OHV3333WRHDFKZHHNGD\
1=P1 Four time bands, two On and two Off
2=P2 Two time bands, one On and one Off
3=P3 Single time band always On
4=P4 Single time band always Off
- 1 4 1 X 16458
254 tUE - 1 4 1 X 16459
255 UEd - 1 4 1 X 16460
256 tHr - 1 4 1 X 16461
257 Fri - 1 4 1 X 16462
258 SAt - 1 4 2 X 16463
259 SUn - 1 4 4 X 16464
There are also avaiables the following variables
Men label Par Label Description U. m.
Range
Default KCTR PW
Address
min max
---Defrosting active or non-active (read-only) -
--
- - - 8967
---On / Off unit (read / write) -
--
- - - 16385
---Mode of operation Summer / Winter (reading and writing) -
--
- - - 16387
75
Section I :: User
EN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RHOSS ELECTA Series and is the answer not in the manual?

RHOSS ELECTA Series Specifications

General IconGeneral
BrandRHOSS
ModelELECTA Series
CategoryHeat Pump
LanguageEnglish

Related product manuals