Rockwell Automation Publication 2198-RM002A-EN-P - October 2017 37
Servo Drive and System Comparison Chapter 2
Table 13 - Kinetix 5700 Input Power UL/CSA Circuit-protection Specifications
Table 14 - Kinetix 5700 Input Power IEC (non-UL/CSA) Circuit-protection Specifications
DC-bus Power Supply
(1)
Cat. No.
(1) For applications that require CSA certification, fuses (Bussmann catalog number 170M1760) must be added to the DC link between the two drive clusters when circuit breakers are used for branch
circuit protection. The DC-bus fuses are not required when AC line fuses are used for branch circuit protection.
Drive Voltage
(three-phase) nom
Bussmann Fuses
Cat. No.
Miniature CB
Cat. No.
Motor Protection CB,
Self Protected CMC
Cat. No.
Molded Case CB
Cat. No.
2198-P031
324…528V AC
LPJ-15SP (15 A) 1489-M3D250 140M-D8E-C25 140G-G6C3-C25
2198-P070 LPJ-40SP (40 A) 1489-M3D400 140M-F8E-C45 140G-G6C3-C50
2198-P141 LPJ-70SP (70 A) 1489-M3D630 – 140G-G6C3-C90
2198-P208 LPJ-100SP (100 A) – – 140G-G6C3-D12
DC-bus Power Supply
Cat. No.
Drive Voltage
(three-phase) nom
DIN gG Fuses
Amps, max
Miniature CB
Cat. No.
Motor Protection CB
Cat. No.
Molded Case CB
Cat. No.
2198-P031
324…528V AC
16 1489-M3D250 – 140M-D8E-C25 140G-G6C3-C25
2198-P070 40 – 1492-SPM3D400 140M-F8E-C45 140G-G6C3-C50
2198-P141 75 – 1492-SPM3D630 140MG-H8E-C60 140G-G6C3-C90
2198-P208 110 – – 140MG-H8E-D10 140G-G6C3-D12