I-35
P
RODUCTS
3) Select preliminary outdoor units
Ô Before selecting outdoor units, decide the permissible combination rates for indoor and outdoor unit.
➊ Determining permissible combination rates for indoor and outdoor units: Below 110%
❷ Calculate the sum of total capacity of the selected indoor units: 52.9kW (Refer to the table below)
52.9kW = [3.6kW + 7.1kW + 5.6kW + 7.1kW + 11.2kW + 7.1kW + 11.2kW]
❸ Select outdoor units
❹ Calculating actual combination rates of indoor and outdoor units
As outdoor unit RVXVHT180✴✴’s cooling capacity is 50.4kW,
Zone A B C D E F G
Total cooling load (kW) 3.3 6.3 4.5 7.1 10.4 7.0 10.0
Sensible heat load of
cooling (kW)
2.2 5.0 3.0 4.9 8.0 5.1 7.0
Indoor unit type Vivace Slim duct Mini 4way 4way Slim duct Ceiling 4way
Determined model
AVXWVH036 AVXDSH071 AVXCMH056 AVXC4H071 AVXDSH112 AVXTFH071 AVXC4H112
Indoor unit capacity (kW) 3.6 7.1 5.6 7.1 11.2 7.1 11.2
As the sum of all
indoor unit capacity
≤
Outdoor unit capacity
Permissible
combination rate,
All indoor unit capacity (52.9kW)
Actual combination rate is
=
Outdoor unit capacity (50.4kW)
approx. 105%.
As the sum of all
indoor unit capacity
≤
permissible combination rate
Outdoor unit
capacity.
OUTDOOR TYPE
Power Supply
Mode
Model
Performance
RVXVH(R)T160GE
3, 380~415, 50
HP/HR
16
44.8
152,900
50.4
172,000
RVXVH(R)T180GE RVXVH(R)T200GE
3, 380~415, 50
HP/HR
20
56.0
191,000
63.0
215,000
RVXVH(R)T220GE
3, 380~415, 50
HP/HR
22
61.6
210,100
69.3
236,500
ø, V, Hz
-
HP
kW
Btu/h
✻
4
kW
Btu/h
-
Cooling
✻
1)
Heating
✻
2)
Horse Power
Capacity
Capacity Control Step
❈ Therefore, as 52.9kW/1.1 should meet outdoor unit capacity and less ( 52.9 kW/1.1 ≤ outdoor unit capacity), cooling
capacity of outdoor unit should be larger than 48.1kW.
Hence, select the outdoor unit RVXVHT180GE(refer to the table below).
3, 380~415, 50
HP/HR
18
50.4
171,900
56.7
193,500
1. products(01~41) 3/14/08 22:01 Page 35